Strany 1 - IInntteelllliiss

IInntteelllliissDDeevviicceeNNeett NNeettwwoorrkk MMoonniittoorr MMooddeellss 77660044,, 77664444 && 77667799 Installation and Operati

Strany 2 - Revision History

1.5.2 DeviceNet Features Table 5 DeviceNet Features Device Type Generic Explicit Peer to Peer Messaging No I/O Peer to Peer Messaging No Configur

Strany 3 - 1 Introduction

2 Installation Instructions Mounting 2-2 Pneumatic Connections 2-3 Tubing and Fittings 2-3 Porting 2-4 Maintenance 2-4 Switch Adjustment 2-5 W

Strany 4 - 1.3 About DeviceNet

IMPORTANT: If the valve monitor is already in the field mounted on an actuator and valve, please follow the field wiring instructions in Section 2.

Strany 5

Figure 3 2.2 Pneumatic Connections Personal injury and/or property damage may occur from loss of process control if the supply medium is not c

Strany 6 - Table 1

2. Apply sealant/lubricant or Teflon tape to the male pipe threads. With any sealant tape, the first one or two threads should be left uncovered to

Strany 7 - Table 2

2.3 Switch Adjustment Switches are factory set. If you need to adjust switches for any reason follow instructions below. For steps 1-8 refer to F

Strany 8 - Table 3

2.4 Wiring Instructions All wiring must be in accordance with National Electrical Code (ANSI-NFPA-70) for the appropriate area classifications.

Strany 10 - Table 6

2.4.1 DPAC Connector Pin-out Diagrams Tech-309 2-8

Strany 11 - 2 Installation Instructions

2.5 DeviceNet Cabling Information Correct termination of the trunk and total trunk and drop limits for the baud rate the network is to run at mus

Strany 12 - 2.1 Mounting

Revision History Revision 1.0 1 June, 2004 Initial Version Revision 1.1 10 February, 2005 Document was updated to reflect new PCB design, additio

Strany 13 - 2.2 Pneumatic Connections

3 DPAC Configuration Communication Settings 3-2 Baud Rate and Address via the DIP Switch 3-2 Baud Rate and Address via the Bus 3-4 Tech-309 3-1

Strany 14 - 2.2.3 Maintenance

3.1 Communication Settings For the appropriate DIP switch settings for the address and baud rate of the DPAC refer to Figure 15 and Tables 9 and 10.

Strany 15 - 2.3 Switch Adjustment

Table 10-a Switch S1 MAC ID Returned Value SW6 SW5 SW4 SW3 SW2 SW1 OFF OFF OFF OFF OFF OFF 0 0x00 OFF OFF OFF OFF OFF ON 1 0x01 OFF OFF OFF OFF

Strany 16 - 2.4 Wiring Instructions

Table 10-b Switch S1 MAC ID Returned Value SW6 SW5 SW4 SW3 SW2 SW1 ON OFF ON ON OFF ON 45 0x2D ON OFF ON ON ON OFF 46 0x2E ON OFF ON ON ON ON 47

Strany 17 - Tech-309

Appendix A Contact Information USA Westlock Controls Corp. 280 Midland Ave. Saddle Brook, NJ 07663 Phone: (201) 794-7650 • Fax: (201) 794-0913 Emai

Strany 18

Tech-309 - 1 - Appendix B Westlock Controls Corporation DeviceNet DN-WLCIO Device Specifications Publication # 07241992 Date 10/09/200

Strany 19 - Table 8

Tech-309 - 2 - Device Profile The DN-WLCIO is the General Purpose Discrete I/O Device (Profile Number 7) Objects Present in Device Object name

Strany 20 - 3 DPAC Configuration

Tech-309 - 3 - Identity Object Class Code: 01(0x01) Identity Object Class Attributes Class=1, Instance=0, Attribute=1,

Strany 21 - Table 9

Tech-309 - 4 - Message Router Object Class Code: 02(0x02) Message Router Object Class Attributes Class Implementation is based

Strany 22 - Table 10-a

Tech-309 - 5 - DeviceNet Object Class Code: 03(0x03) DeviceNet Object Class Attributes Class=3, Instance=0, Attribute=1Attribute ID Ac

Strany 23 - Table 10-b

1 Introduction Scope of Manual 1-2 Symbols Used in this Document 1-2 About DeviceNet 1-2 Westlock Intellis DeviceNet Module EL-40092 1-3 Modul

Strany 24 - Appendix A

Tech-309 - 6 - ** Baud Rate is settable through DeviceNet only if switch S1 positions 7 and 8 are both in the ON position. See Table below.

Strany 25 - Device Specifications

Tech-309 - 7 - Assembly Object Class Code: 04(0x04) Assembly Object Class Attributes Implementation is based on the Static As

Strany 26 - Objects That Effect Behavior

Tech-309 - 8 - Assembly Object Instance #4 Attributes (Instance #4 is type: 8 point with No Status Bit) Class=4, Instance=4, Attribute=

Strany 27 - 01(0x01)

Tech-309 - 9 - Assembly Object Instance #32 Attributes (Instance #32 is type: 2-Point Output, and is used only when the device has 2 outputs or

Strany 28 - 02(0x02)

Tech-309 - 10 - Assembly Object Instance #33 Attributes (Instance #33 is type: 4-Point Output, and is used only when the device has 4 outputs.

Strany 29 - 03(0x03)

Tech-309 - 11 - Connection Object Class Code: 05(0x05) Connection Object Class Attributes Implementation is based on revision 0

Strany 30

Tech-309 - 12 - Connection Object Instance #1 Attributes (Explicit Message Connection – Instance #1) Class=5, Instance=1, Attribut

Strany 31 - 04(0x04)

Tech-309 - 13 - Connection Object Instance #2 Attributes (Poll I/O connection - Instance #2) Class=5, Instance=2, Attribut

Strany 32

Tech-309 - 14 - Discrete Input Point Object Class Code: 08(0x08) Discrete Input Point Object Class Attributes Class=8, Instance=0, Attri

Strany 33 - Attribute #3 (Data)

Tech-309 - 15 - Discrete Output Point Object Class Code: 09(0x0A) Discrete Output Point Object Class Attributes Class=9, Instanc

Strany 34

1.1 Scope of Manual This manual contains installation, configuration and specification data for the DPAC DeviceNet valve controller. This manual a

Strany 35 - 05(0x05)

design and implement, DeviceNet has the capability to interconnect complex as well as simple devices to the same network, easily accommodating both a

Strany 36

1.4.1 Module Bit Map Table 1 I/O TYPE MODULE REFERENCE BITMAP OF DATA INSTANCE #4 (8-POINT INPUT WITH NO STATUS) ATTRIBUTE #3 (DATA) INPUT 0 Hall

Strany 37 - Tech-309 - 13

Table 2 Value Meaning 1 Auto Delete: The Connection Class automatically deletes the Connection if it experiences an IWT timeout. This is the default

Strany 38

Table 3 Module p/n LED State Indicates Off There is no power applied to the device. Green Device is operating in a normal condition. Flashing Gre

Strany 39 - 09(0x0A)

1.4.4 Module Layout J1 Figure 1- EL-40092 1.5 Device Specifications 1.5.1 Specifications Table 4 Round Physical Media Shielded 2 twisted pairs f